sales@transformertraders.com(248) 250-0407
Home/Inventory/New & unused/GE Grid Solutions 250 MVA
New & unused

GE Grid Solutions 250 MVA Power Transformer
132 kV / 33 / 33 kV

132 kV high side / 33 / 33 kV low side

PA585-01..02 · Windyhill BESS · 50 Hz

Manufacturer technical records

New and unused. The listed 250 MVA, 132/33–33 kV ratings follow the technical datasheet and approved dimensional drawing. The supplied nameplate is marked IN WORK and contains conflicting power, voltage, cooling and insulation values. Review the nameplate differences and transcription.

Equipment specifications

Manufacturer
GE Grid Solutions
Application
Power transformer
Power rating
250 MVA
High-side voltage
132 kV
Low-side voltage
33 / 33 kV
Catalog condition
New & unused
Listed quantity
On request
Tap changer
MR OLTC; ±12 × 1.75% on HV
Service history
New and unused
Rating basis
Technical datasheet and approved dimensional drawing; IN WORK nameplate differences shown below
Document project reference
PA585-01..02 / 5337PA585-01..02
Manufacturer / origin (nameplate)
Grid Solutions Enerji Endüstrisi A.Ş., 41410 Gebze/Kocaeli, Türkiye; made in Turkey
Phase / frequency
Three-phase / 50 Hz
Winding ratings (HV / LV1 / LV2)
250 / 125 / 125 MVA
Winding voltages (no load)
132 / 33 / 33 kV
Vector group
YNd1d1
Cooling (datasheet designation)
ONAN (75%) / ODAN (100%)
HV on-load regulation
±12 steps × 1.75%
OLTC
MR VRL III 1600Y-170/E-14 27 3W
OLTC motor drive (drawing)
MR ETOS SIDE DRIVE ED
Rated currents (drawing)
HV: 1,093.5 A; LV: 2,186.9 A
Manufacturing standard
IEC 60076
Ambient temperature
−25°C to +40°C
Installation altitude
Below 1,000 m
Temperature rise (oil / winding / hot spot)
60 / 70 / 78 K
No-load current at rated voltage
0.20%
Auxiliary losses
10 kW, excluding spare
Peak efficiency index (datasheet)
>99.797% at Tap 13; Tier II 2021 basis
Sound pressure, ODAN including load noise
77 dB(A) at 2 m; 80 dB(A) at 1 m
HV insulation (Um / AC / BIL)
145 / 230 / 550 kV
HV-neutral insulation (Um / AC / BIL)
145 / 230 / 550 kV
LV1 and LV2 insulation (Um / AC / BIL)
36 / 70 / 170 kV
HV bushings
GE RPV / Passoni Villa PNO 145.650.2500; oil-air, OIP condenser, porcelain
HV-neutral bushing
GE RPV / Passoni Villa PNO 145.650.1250; oil-air, OIP condenser, porcelain
LV1 / LV2 bushings
30 NF 3150 A; oil-air, solid DIN, porcelain
Maximum magnetic induction at rated voltage
≤1.71 T
Overall dimensions, approximate (L × W × H)
19,600 × 7,800 × 8,700 mm
Transport dimensions, approximate (L × W × H)
9,000 × 3,500 × 4,600 mm
Total weight, approximate
283,000 kg
Oil weight, approximate
66,000 kg
Active-part / untanking weight, approximate
139,000 kg
Shipping weight without oil, approximate
177,000 kg
Transport gas
Nitrogen
Drawing issuer
GE Grid Solutions, Gebze/Kocaeli, Türkiye
Drawing reference / status
T01105329, Revision 00, Approved, July 18, 2024
Datasheet file revision / date
R0 / September 19, 2024; date supplied in filename
Service (nameplate)
Continuous
Oil type (nameplate)
NYNAS NYTRO LYRA X
Nameplate drawing / status
T01106880, version 00.4; IN WORK (digitally signed)
Serial number / manufacturing year
Unfilled on supplied nameplate; to be entered after acceptance tests

Nameplate data & document differences

The supplied rating-plate drawing is marked IN WORK. Its main rating table lists 91/135 MVA and 110/15 kV, while its separate HV tap schedule has a 132 kV neutral position and 1,093.5 A in the ONAF column. These fields do not agree within the plate. The listing uses the 250/125/125 MVA, 132/33/33 kV design stated in the technical datasheet and approved dimensional drawing. A final, corrected unit-specific nameplate is required to resolve these differences.

Differences between the supplied technical datasheet and IN WORK nameplate
FieldTechnical datasheetIN WORK nameplate main table
Rated powerHV / LV1 / LV2: 250 / 125 / 125 MVAHV and LV1–LV2 columns each show 91,000 kVA ONAN / 135,000 kVA ONAF
Rated voltageHV / LV1 / LV2: 132 / 33 / 33 kVHV: 110 kV; LV1–LV2: 15 kV
CoolingONAN (75%) / ODAN (100%)ONAN / ONAF
Oil / winding temperature rise60 / 70 K; hot spot 78 K58 / 63 K; hot spot not stated
HV insulation, Um / AC / impulse145 / 230 / 550 kV123 / 230 / 550 kV
HV-neutral insulation, Um / AC / impulse145 / 230 / 550 kV— / 230 / 550 kV
LV1 / LV2 insulation, Um / AC / impulse36 / 70 / 170 kV17.5 / 38 / 95 kV
Full nameplate transcription: identification, ratings & insulation

Values below reproduce the supplied IN WORK plate. An asterisk means the value has not been entered; a dash is retained where shown.

Manufacturer
Grid Solutions Enerji Endüstrisi A.Ş., 41410 Gebze/Kocaeli, Türkiye
Country marking
MADE IN TURKEY
Transformer type / phases
Power / 3
Frequency / vector group
50 Hz / YNd1d1
Service / standard
Continuous / IEC 60076
Serial number / year of manufacture
* / * — not filled in
Maximum ambient temperature
40°C
Oil / winding temperature rise
58 / 63 K
Total / core and coil / oil weight
283 / 139 / 66 metric tonnes
Transport weight without oil
177 metric tonnes
Oil type
NYNAS NYTRO LYRA X
On-load tap changer
MR, VRL III 1600Y-170/E-14 27 3W
OLTC rated current / Um / serial number
1,600 A / 170 kV / * (not filled in)
Overload standard
IEC 60076-7
Vacuum capability
Tank, radiators and conservator are vacuum proof
Maximum short-circuit duration
2 seconds
Maximum symmetrical short-circuit current
HV: *; LV1–LV2: * — not filled in
Short-circuit impedance
HV/LV1–LV2, 135,000 kVA base; positions 1, 11 and 21: * — not filled in
Missing-value note
The plate says missing values are to be written after acceptance tests
Drawing / version / status
T01106880 / 00.4 / IN WORK (digitally signed)
Project / file name
WINDYHILL / PA585_01_RATING_PLATE
Plate format / template reference
D297 × 420 / T00749789
Nameplate main rating and current table — conflicting values retained as supplied
CoolingHV powerLV1–LV2 powerHV voltageLV1–LV2 voltageHV current, pos. 1 / 11 / 21LV1–LV2 current
ONAN91,000 kVA91,000 kVA110,000 V15,000 V415.3 / 477.6 / 561.9 A1,751.3 A
ONAF135,000 kVA135,000 kVA110,000 V15,000 V616.1 / 708.6 / 833.6 A2,598.1 A
Nameplate insulation levels, in kV
WindingUmLI/CWAC
HV123550230
HV-N—550230
LV1 / LV217.59538
HV tap schedule — all 25 positions and neutral transitions

The plate shows positions 1–25 plus 13A and 13B. The neutral voltage is 132,000 V; the endpoints are 159,720 and 104,280 V. ONAN and ONAF are the column labels printed on this plate. They differ from the datasheet cooling designation.

HV tap schedule transcribed from the supplied nameplate
PositionVoltage, VCurrent ONAN, ACurrent ONAF, ASelectorPre-selector
1159,720677.8903.71K+
2157,410687.7917.02K+
3155,100698.0930.63K+
4152,790708.5944.74K+
5150,480719.4959.25K+
6148,170730.6974.16K+
7145,860742.2989.67K+
8143,550754.11005.58K+
9141,240766.41021.99K+
10138,930779.21038.910K+
11136,620792.41056.511K+
12134,310806.01074.712K+
13A132,000820.11093.513K+
13132,000820.11093.5KTransition
13B132,000820.11093.51K−
14129,690834.71112.92K−
15127,380849.81133.13K−
16125,070865.51154.14K−
17122,760881.81175.85K−
18120,450898.71198.36K−
19118,140916.31221.87K−
20115,830934.61246.18K−
21113,520953.61271.59K−
22111,210973.41297.910K−
23108,900994.11325.411K−
24106,5901015.61354.112K−
25104,2801038.11384.113K−

At position 13, the selector is K and the diagram shows the transition between K+ and K−. The original PDF retains the complete tap-changer connection diagram.

Current transformers & winding connections
Nameplate current-transformer schedule
CTClassTerminal / ratio (A/A)Burden, VATechnical parameters
T1PX-B(SPT)S1–S2: 1000/1; S1–S3: 1200/1—Min. Ek 700 V; max. Ie at Ek 80 mA; max. Rct at 75°C 4.5 Ω
T2Cl.1 5P20S1–S2: 600/1; S1–S3: 1200/130—
T3, T4PX-B(NG)S1–S2: 500/1; S1–S3: 1000/1——
T53S1–S2: 1450/210Not stated
T6, T73S1–S2: 2400/210Not stated
T8Cl.1 5P20S1–S2: 1000/1; S1–S3: 2000/1——
T9PX-B(NG)S1–S2: 600/1; S1–S3: 1200/1——

The winding diagram identifies HV terminals 1U, 1V, 1W and neutral 1N; the two delta windings use 2U, 2V, 2W and 3U, 3V, 3W. The stated vector group is YNd1d1. CT locations, P1/P2 polarity, secondary terminals and OLTC connections are shown in the attached original nameplate drawing.

250 MVA with two 33 kV windings

This GE Grid Solutions three-phase power-transformer design combines a 132 kV high-voltage winding with two 33 kV low-voltage windings, each rated 125 MVA. The supplied documentation identifies the Windyhill BESS project and YNd1d1 connections, with on-load voltage regulation on the HV side.

Rated frequency: 50 Hz. Suitability for a 60 Hz system is not established by these documents. Have the project engineer review frequency, winding configuration, insulation, impedance and protection requirements before selection.

Losses and impedance

Datasheet values by tap position
ParameterTap 01Tap 13Tap 25
No-load loss at 1.0 Un, kW110 (G)110 (G)110 (G)
Load loss at 75°C, 250/125–125 MVA base, kW575 (I)585 (G)850 (I)
Total loss including auxiliaries, kW695 (I)705 (G)970 (I)
HV–LV1 impedance at 75°C, 125 MVA base15.0% (I)14.0% (G)13.5% (I)
HV–LV2 impedance at 75°C, 125 MVA base15.0% (I)14.0% (G)13.5% (I)

G = designated guaranteed in the manufacturer datasheet; I = supplied for information. IEC tolerances apply to guaranteed values. These are design-document values, not measured factory-test results or a separate Transformer Traders performance guarantee. LV1–LV2 impedance is stated as 26.5% on a 125 MVA base.

Peak efficiency calculation — datasheet page 3
P0 / Pc0 / PcK
110 / 0 / 0 kW
kPEI
0.43
Pk / Sr
585 kW / 250 MVA
PEI (calculation sheet)
0.99797; the characteristics table separately specifies >99.797%

Documented fittings and controls

The approved drawing identifies a main-tank conservator and air cell, radiator assembly, main-tank Buchholz relay, OLTC protection relay, oil-level indicators, pressure-relief devices, oil and winding temperature instruments, core-earthing terminals, and a control cabinet for cooling units and devices. Lifting lugs, jacking pads, pulling eyes and wheels are also shown.

The drawing identifies a Calisto 2 oil-monitoring device but expressly marks it outside GE scope. Inclusion of this device or other accessories in the sale must be established in the quotation. Cooling is reproduced as ONAN (75%) / ODAN (100%) from the datasheet. The supplied IN WORK nameplate instead says ONAN / ONAF; the final cooling schedule and corrected nameplate remain to be confirmed.

Transport and project coordination

The documented shipping envelope is approximately 9.0 m long × 3.5 m wide × 4.6 m high, at 177 metric tonnes without oil. The complete assembly is approximately 19.6 m long × 7.8 m wide × 8.7 m high, with an approximate total mass of 283 metric tonnes. These are planning dimensions and weights; confirm the shipment breakdown, accessory loads and approved lifting plan before booking transport.

Commercial information

Contact Transformer Traders for current pricing, quantity, location, release schedule and included scope. The project notation PA585-01..02 is a document reference and does not establish the number of units offered. The supplied nameplate leaves serial numbers and manufacturing year unfilled. The transformer is offered new and unused.

Listing details

New and unused GE Grid Solutions three-phase power transformer; datasheet rating 250 MVA HV / 125 MVA LV1 / 125 MVA LV2, 132/33–33 kV, 50 Hz, YNd1d1. Datasheet cooling ONAN (75%) / ODAN (100%); HV OLTC regulation ±12 × 1.75%. Project PA585-01..02, Windyhill BESS. Supplied IN WORK rating plate T01106880 contains conflicting electrical values; headline ratings follow the technical datasheet and approved drawing T01105329. Price, quantity and release schedule on inquiry.

Winding connections, secondary options, included accessories, and tap-changer details must be checked against the unit-specific nameplate and drawings. The description above preserves the listed configuration.

Request the technical package

Ask our team for the records available for this equipment and confirmation of its current status.

  • Nameplate & winding diagram
  • General arrangement drawings
  • Equipment photographs
  • Factory or field test reports
  • Condition & service history
  • Dimensions & shipping weights

Document availability varies by unit. Pricing, location, lead time, warranty, and delivery scope are provided with the quotation.

How do I confirm availability?

Email the equipment ID or call (248) 250-0407. Equipment is subject to prior sale. Current availability and allocation are confirmed in writing.

Can you coordinate transportation and installation?

Yes. We coordinate shipment preparation, oil services, heavy haul, rigging, placement, and qualified installation support as an agreed project scope. Explore full-service solutions.

What purchase and warranty options apply?

Terms depend on the equipment, condition, seller, and agreed scope. Review purchase options and request a unit-specific quotation.

Attached manufacturer documents

All three supplied PDFs are attached in their original form.

Continue your search

Related equipment

View category inventory