345 kV high side / 34.5 kV low side
138 / 184 / 230 MVA · 345 / 34.5 kV · 13.8 kV tertiary
New and unused three-phase step-up transformer with copper windings, ONAN/ONAF1/ONAF2 cooling and an HV on-load tap changer. Made in the USA. Pricing, location and delivery available on request.
Select the photograph to view the original image. Nameplate and outline drawings are linked above and attached below.
The nameplate lists the same MVA ratings for the 345 kV HV and 34.5 kV LV windings. The tertiary voltage is 13.8 kV; a separate tertiary MVA rating is not stated.
| Cooling stage | Rated capacity at 65°C rise | HV current at 345 kV | LV current at 34.5 kV |
|---|---|---|---|
| ONAN | 138 MVA | 231 A | 2,309 A |
| ONAF1 | 184 MVA | 308 A | 3,079 A |
| ONAF2 | 230 MVA | 385 A | 3,849 A |
Vector group: the dedicated nameplate box reads YNyn0d11, while the drawing type lines read YN0yn0d1. The tertiary phase displacement requires manufacturer confirmation; both original drawings are attached.
The HV tap schedule spans 310,500–379,500 V around the nominal 345,000 V rating. This corresponds to ±10% in 0.625% voltage steps. The nameplate identifies NR, N and NL neutral entries at 345,000 V.
| HV voltage (V) | 138 MVA (A) | 184 MVA (A) | 230 MVA (A) |
|---|---|---|---|
| 379,500 | 210 | 280 | 350 |
| 377,344 | 211 | 282 | 352 |
| 375,188 | 212 | 283 | 354 |
| 373,031 | 214 | 285 | 356 |
| 370,875 | 215 | 286 | 358 |
| 368,719 | 216 | 288 | 360 |
| 366,562 | 217 | 290 | 362 |
| 364,406 | 219 | 292 | 364 |
| 362,250 | 220 | 293 | 367 |
| 360,094 | 221 | 295 | 369 |
| 357,938 | 223 | 297 | 371 |
| 355,781 | 224 | 299 | 373 |
| 353,625 | 225 | 300 | 376 |
| 351,469 | 227 | 302 | 378 |
| 349,312 | 228 | 304 | 380 |
| 347,156 | 230 | 306 | 383 |
| 345,000 | 231 | 308 | 385 |
| 342,844 | 232 | 310 | 387 |
| 340,688 | 234 | 312 | 390 |
| 338,531 | 235 | 314 | 392 |
| 336,375 | 237 | 316 | 395 |
| 334,219 | 238 | 318 | 397 |
| 332,062 | 240 | 320 | 400 |
| 329,906 | 242 | 322 | 403 |
| 327,750 | 243 | 324 | 405 |
| 325,594 | 245 | 326 | 408 |
| 323,438 | 246 | 328 | 411 |
| 321,281 | 248 | 331 | 413 |
| 319,125 | 250 | 333 | 416 |
| 316,969 | 251 | 335 | 419 |
| 314,812 | 253 | 337 | 422 |
| 312,656 | 255 | 340 | 425 |
| 310,500 | 257 | 342 | 428 |
The outline drawing gives the following dimensions. Its stated dimensional tolerance is ±2%, and its notes say dimensions and weights may change after detailed design. Confirm the final shipping configuration before arranging transport.
| Configuration | Length | Width | Height |
|---|---|---|---|
| Overall assembled | 484.25 in / 12,300 mm | 311.02 in / 7,900 mm | 393.69 in / 10,000 mm |
| Shipping | 362.2 in / 9,200 mm | 139.76 in / 3,550 mm | 191.99 in / 4,877 mm |
| Component / basis | Weight / oil volume |
|---|---|
| Core and coil | 237,658 lb |
| Tank and fittings | 106,924 lb |
| Untanking | 249,780 lb |
| Insulation | 16,652 lb |
| Radiator, each | 1,810 lb |
| Conservator | 6,614 lb |
| Oil in radiators at 20°C | 12,751 lb / 1,771 gal |
| Oil in conservator at 20°C | 4,680 lb / 650 gal |
| Total insulating oil at 20°C | 123,127 lb / 16,878 gal |
| Total transformer weight | 467,709 lb |
| Shipping weight without oil | 295,860 lb |
The nameplate also includes a separate table titled “Calculated Value of Weight.” The outline contains another weight schedule. These values are retained by source below; they are not interchangeable shipping instructions.
| Measurement | Main nameplate table | Calculated table on nameplate | Outline drawing |
|---|---|---|---|
| Total weight | 467,709 lb | 471,348 lb | 471,342 lb / 213,800 kg |
| Total insulating oil | 123,127 lb / 16,878 gal | 126,764 lb / 17,661 gal | 126,764 lb / 57,500 kg |
| Shipping without oil | 295,860 lb | 295,860 lb | 295,856 lb / 134,200 kg |
| Location / use | Current ratio | Class |
|---|---|---|
| HV protection, C1–C6; HV neutral, C11–C12 | 2,000:5 multiratio | C800 |
| LV protection, C13–C21; LV neutral, C24–C25 | 4,000:5 multiratio | C800 |
| Additional HV CTs, C7–C9 | 400:5 single ratio | 0.3B-1.8 |
| HV winding temperature, C10 | 385:5 single ratio | 1.2B-0.9 |
| LV AVR / winding temperature, C22–C23 | 3,900:5 single ratio | 0.3B-1.8 |
The continuous thermal current rating factor is 2.0 for all CTs. Full multiratio terminal connections are shown in the nameplate PDF.
These items are identified on the supplied outline. Confirm the included shipment scope and accessory condition with the quotation.
Winding connections, secondary options, included accessories, and tap-changer details must be checked against the unit-specific nameplate and drawings. The description above preserves the listed configuration.
Review the transformer procurement checklist, the technical documentation guide, and delivery planning requirements.
Looking for a different unit? Browse new & unused inventory and pre-owned transformers, or ask about additional sourcing options.
Ask our team for the records available for this equipment and confirmation of its current status.
Document availability varies by unit. Pricing, location, lead time, warranty, and delivery scope are provided with the quotation.
Email the equipment ID or call (248) 250-0407. Equipment is subject to prior sale. Current availability and allocation are confirmed in writing.
Yes. We coordinate shipment preparation, oil services, heavy haul, rigging, placement, and qualified installation support as an agreed project scope. Explore full-service solutions.
Terms depend on the equipment, condition, seller, and agreed scope. Review purchase options and request a unit-specific quotation.
Original supplier PDFs and the equipment photograph are available below.