sales@transformertraders.com(248) 250-0407
Home/Inventory/Additional transformers/REX-G042095-4
Condition on request

REX POWER MAGNETICS 225 kVA
0.48 kV / 0.416 kV dry-type isolation transformer for sale

0.48 kV high side / 0.416 kV low side

Equipment ID: REX-G042095-4

Equipment specifications

Manufacturer
REX POWER MAGNETICS
Equipment ID
REX-G042095-4
Application
Dry-type isolation transformer
Power rating
225 kVA
High-side voltage
0.48 kV
Low-side voltage
0.416 kV
Catalog condition
Condition on request
Listed quantity
On request
Manufacture year
On request
Tap changer
Five primary connection taps; confirm safe operating procedure with OEM instructions
Manufacturer / division
Rex Power Magnetics, Transfactor Industries Inc.
Catalog number
BA225H-N/K13/Y2/Z3
Serial number
G 042095-4
Country of manufacture
Canada; Concord, Ontario
Type / enclosure
ANN / Type 3R
Phase / frequency
3-phase isolation / 60 Hz
Primary connection
480 V delta; H1–H2–H3
Secondary connection
416Y / 240 V; X0–X1–X2–X3
Impedance
4.0% at 170 °C
Insulation class
220 °C
Temperature rise
150 °C
BIL
10 kV
K-factor
13; nameplate says suitable for nonsinusoidal current load not exceeding K-13
Weight
1,771 lb
Primary taps
105%, 102.5%, 100%, 97.5%, 95%
Tap connections
1–2, 2–3, 3–4, 4–5, 5–6 respectively
Lug marking
Use with AL9CU lugs
Outdoor installation note
Weather shield kit WP9 recommended on supplied label
Listing marks
UL Listed transformer / CSA marks visible
Manufacture date and service history
Not supplied

225 kVA dry-type isolation transformer

The supplied nameplate identifies a three-phase, 60 Hz Rex Power Magnetics transformer with a 480 V delta primary and 416Y/240 V secondary. It is a dry-type ANN unit with Type 3R enclosure and K-13 marking.

Condition, quantity, manufacture date, included accessories and current availability have not been supplied. Request equipment photographs, dimensions and inspection records before purchase.

Listing details

REX-G042095-4. REX POWER MAGNETICS. 225 kVA. 0.48 kV / 0.416 kV. Based on supplied equipment document. Availability and final configuration require written confirmation.

Winding connections, secondary options, included accessories, and tap-changer details must be checked against the unit-specific nameplate and drawings. The description above preserves the listed configuration.

Request the technical package

Ask our team for the records available for this equipment and confirmation of its current status.

  • Nameplate & winding diagram
  • General arrangement drawings
  • Equipment photographs
  • Factory or field test reports
  • Condition & service history
  • Dimensions & shipping weights

Document availability varies by unit. Pricing, location, lead time, warranty, and delivery scope are provided with the quotation.

How do I confirm availability?

Email the equipment ID or call (248) 250-0407. Equipment is subject to prior sale. Current availability and allocation are confirmed in writing.

Can you coordinate transportation and installation?

Yes. We coordinate shipment preparation, oil services, heavy haul, rigging, placement, and qualified installation support as an agreed project scope. Explore full-service solutions.

What purchase and warranty options apply?

Terms depend on the equipment, condition, seller, and agreed scope. Review purchase options and request a unit-specific quotation.

Continue your search

Related equipment