sales@transformertraders.com(248) 250-0407
Home/Inventory/Pad-mounted/T1501 / T1162-S
Reconditioned

Reconditioned 1000/1120 kVA Substation Transformers
4.16 kV Delta / 480Y/277 V

4.16 kV Delta high side / 480Y/277 V low side

Equipment ID: T1501 / T1162-S

Equipment specifications

Manufacturer
CORE Transformers
Equipment ID
T1501 / T1162-S
Application
Substation transformer
Power rating
1000/1120 kVA
High-side voltage
4.16 kV Delta
Low-side voltage
480Y/277 V
Catalog condition
Reconditioned
Listed quantity
2 total — 1 of each
Manufacture year
On request
Tap changer
±2 × 2.5% taps
Phase
Three-phase
Frequency
60 Hz
High voltage
4160 V Delta
Low voltage
480Y/277 V
HV / LV BIL
60 kV / 30 kV
Cooling class
ONAN
Temperature rise
55/65°C
Insulating fluid
Mineral oil
Taps
2 × 2.5% above and below nominal
Gauges and fittings
Liquid temperature, liquid level, PRD, pressure/vacuum, drain and sample

Two units available

Two reconditioned 1000/1120 kVA, three-phase substation transformers are offered for sale, with one unit of each configuration. Both are rated 4160 V Delta to 480Y/277 V, 60 Hz, with mineral oil and ONAN cooling.

T1501 — aluminum windings

Unit ID
T1501; photographed tag: T1501-S
Quantity
1
Condition
Reconditioned
Winding conductors, HV / LV
Aluminum / aluminum (AL/AL)
HV bushings
ANSI 4
LV bushings
ANSI 2
Impedance
Confirmation required: 6.3% on nameplate; 5.82% in supplied specification

The supplied listing identifies this unit as T1501; its photographed equipment tag reads T1501-S. The supplied specification and nameplate show different impedance values. Request the final unit-specific test report and confirmed impedance when reviewing this unit.

T1162-S — proCORE, copper windings

Unit ID
T1162-S
Quantity
1
Condition / designation
Reconditioned proCORE
Winding conductors, HV / LV
Copper / copper (CU/CU)
HV bushings
ANSI 4 with full-length ATC
LV bushings
ANSI with partial ATC
Impedance
6.2%

Pricing and delivery

Contact Transformer Traders for pricing, equipment location, test records and delivery arrangements. Reference the required unit ID and quantity in your inquiry.

Listing details

Two reconditioned 1000/1120 kVA, three-phase substation transformers: T1501 (photographed tag T1501-S), quantity 1, aluminum/aluminum windings; and T1162-S proCORE, quantity 1, copper/copper windings. Both: 4160 V Delta / 480Y/277 V, 60 Hz, 60/30 kV HV/LV BIL, ±2 × 2.5% taps, 55/65°C temperature rise, ONAN cooling and mineral oil. T1501 impedance requires confirmation: seller specification 5.82%, nameplate 6.3%. T1162-S impedance: 6.2%.

Winding connections, secondary options, included accessories, and tap-changer details must be checked against the unit-specific nameplate and drawings. The description above preserves the listed configuration.

Request the technical package

Ask our team for the records available for this equipment and confirmation of its current status.

  • Nameplate & winding diagram
  • General arrangement drawings
  • Equipment photographs
  • Factory or field test reports
  • Condition & service history
  • Dimensions & shipping weights

Document availability varies by unit. Pricing, location, lead time, warranty, and delivery scope are provided with the quotation.

How do I confirm availability?

Email the equipment ID or call (248) 250-0407. Equipment is subject to prior sale. Current availability and allocation are confirmed in writing.

Can you coordinate transportation and installation?

Yes. We coordinate shipment preparation, oil services, heavy haul, rigging, placement, and qualified installation support as an agreed project scope. Explore full-service solutions.

What purchase and warranty options apply?

Terms depend on the equipment, condition, seller, and agreed scope. Review purchase options and request a unit-specific quotation.

Continue your search

Related equipment

View category inventory